LK13BE

3F Electricity Meter

Product Description

Three-phase electricity meters LK13Bxxxxxxx with direct connection to a 4-wire network are designed to measure active electrical energy in the +A/-A direction (consumption/delivery), up to 4 tariffs, and in accuracy class A or B.

The meters are equipped with an LCD display, optical interface, and a metrological LED (red color). (On request, they can also be equipped with auxiliary terminals for external tariff control – see table).

The tariff registers of the two-tariff meters are switched using auxiliary terminals 13/15. (T1 = HT excited; T2 = NT)

The conformity of the three-phase electricity meters LK13 was verified by the authorized workplace No. 1383 and a certificate of type testing No. 221/12-4981, Addendum 11, dated November 28, 2017, was issued. The manufacturer has issued an EC declaration of conformity with MID 2004/22/EC.

LK13BE

MeasurementActive energy in 3-phase 4-wire network
ClassA or B
DisplayLCD with OBIS designation
TariffsSingle-tariff or two-tariff
Energy calculationA =
Operating temperature range-25 °C to +55 °C
Enclosure ratingIP51
Protection class (electrical)II
Measurement methodStatic electricity meter with current transformers on current inputs
Starting current25 mA
Transition current0.5 A
Minimum current0.25 A
Reference current5 A
Maximum current100 A
Optical communicationEN 62056-21, push, 9600 bps
RS 485 communicationEN 62056-21, push, 9600 bps
Self-consumption of voltage circuit< 1 W and < 10 VA (EN 62053-21, EN 50470-1)
Self-consumption of current circuit< 0.5 VA (EN 62053-21, EN 50470-1)

Scroll to Top